point . unlock the fcp locking nut and slowly turn the pilot adjusting screw cw to increase set flow and ccw to decrease it. allow the -dzb to react and the flow to stabilize, lock the fcp locking nut. iom ir- -dzb trouble-shooting: symptoms cause remedy valve fails to open . cock valve position ( ). . not
sufficient inlet pressure. . not sufficient flow. . adjusting screws. . check cock valve ( ) positioning on auto. . check for sufficient inlet pressure. . create demand/flow, confirm pilot setting. . check that the pilot adjusting screw is not loose. valve fails to close . control circuit is clogged...
https://www.bermad.com/wp-content/uploads/2016/05/IR-172-bDZ.pdf
counter - clock-wise to decrease it. allow the - -kx to react the pressure to stabilize. . after the pressure is stabilized, lock the pilot locking nut and open fully the downstream isolating valve. iom ir- - -kx trouble-shooting: symptoms cause remedy valve fails to open . hydraulic control command . not
sufficient inlet pressure. . not sufficient flow. . adjusting screws. . check existence of hydraulic command in the relay. . check for sufficient inlet pressure. . create demand/flow, confirm pilot setting. . check that the pilot adjusting screw is not loose. valve fails to close . hydraulic control...
https://www.bermad.com/wp-content/uploads/2016/05/IR-420-54-KX.pdf
counter - clock-wise to decrease it. allow the - -bk to react the pressure to stabilize. . after the pressure is stabilized, lock the pilot locking nut and open fully the downstream isolating valve. iom ir- - -kb trouble-shooting: symptoms cause remedy valve fails to open . hydraulic control command . not
sufficient inlet pressure. . not sufficient flow. . adjusting screws. . check existence of hydraulic command in the relay. . check for sufficient inlet pressure. . create demand/flow, confirm pilot setting. . check that the pilot adjusting screw is not loose. valve fails to close . hydraulic control...
https://www.bermad.com/wp-content/uploads/2016/05/IR-420-54-bK.pdf
is stabilized, lock the pilot locking nut and open fully the upstream isolating valve. . connect the remote control to the opening port in the shuttle valve ( –x-p). iom ir- - -kxz trouble-shooting: symptoms cause remedy valve fails to open . cock valve ( ) is closed. . hydraulic control command. . not
sufficient inlet pressure. . not sufficient flow. . adjusting screws. . confirm that cock valve ( ) handle is turn to auto. . check no existence of hydraulic pressure command in the shuttle valve. . check for sufficient inlet pressure. . create demand/flow, confirm pilot setting. . check that the pilot...
https://www.bermad.com/wp-content/uploads/2016/05/IR-430-50-KXZ.pdf
is stabilized, lock the pilot locking nut and open fully the upstream isolating valve. . connect the remote control to the opening port in the shuttle valve ( –x-m). iom ir- - -rxz trouble-shooting: symptoms cause remedy valve fails to open . cock valve ( ) is closed. . hydraulic control command. . not
sufficient inlet pressure. . not sufficient flow. . adjusting screws. . confirm that cock valve ( ) handle is turn to auto. . check no existence of hydraulic pressure command in the shuttle valve. . check for sufficient inlet pressure. . create demand/flow, confirm pilot setting. . check that the pilot...
https://www.bermad.com/wp-content/uploads/2016/05/IR-430-50-RXZ.pdf
adjusting screw clock-wise to increase set pressure and counter-clock-wise to decrease it. . after the pressure is stabilized, lock the pilot locking nut and open fully the upstream isolating valve. iom ir- - -kx trouble-shooting: symptoms cause remedy valve fails to open . hydraulic control command . not
sufficient inlet pressure . not sufficient flow . adjusting screws . check existence of hydraulic pressure command in the relay ( -pz). . check for sufficient inlet pressure. . create demand/flow, confirm pilot setting. . check that the pilot adjusting screw is not loose. valve fails to close . hydraulic...
https://www.bermad.com/wp-content/uploads/2016/05/IR-430-54-KX.pdf
flow and counter clock-wise to decrease it. allow the ir- - -kub to react and the flow to stabilize. . after the flow is stabilized lock the pilot nut and open fully the downstream isolating valve. iom ir- - -kub trouble-shooting: symptoms cause remedy valve fails to open . hydraulic control command . not
sufficient inlet pressure. . not sufficient flow. . adjusting screws. . check existence of hydraulic command in the relay. . check for sufficient inlet pressure. . create demand/flow, confirm pilot setting. . check that the pilot adjusting screw is not loose. valve fails to close . hydraulic control...
https://www.bermad.com/wp-content/uploads/2016/05/IR-470-54-bKU.pdf
flow and counter clock-wise to decrease it. allow the ir- -kuzb to react and the flow to stabilize. . after the flow is stabilized lock the pilot nut and open fully the downstream isolating valve. iom ir- -kuzb trouble-shooting: symptoms cause remedy valve fails to open . cock valve position ( ). . not
sufficient inlet pressure. . not sufficient flow. . adjusting screws. . check cock valve ( ) positioning on auto. . check for sufficient inlet pressure. . create demand/flow, confirm pilot setting. . check that the pilot adjusting screw is not loose. valve fails to close . control circuit is clogged...
https://www.bermad.com/wp-content/uploads/2016/05/IR-470-bKUZ.pdf
pressure is stabilized lock the pilot nut. . open fully the downstream isolating valve. . connect the remote control to the opening port in the hydraulic relay valve ( -m). iom ir- -m - -r trouble-shooting: symptoms cause remedy valve fails to open . cock valve ( ) is closed. . hydraulic control command . not
sufficient inlet pressure. . not sufficient flow. . adjusting screws. . confirm that cock valve handle is parallel to valve body. . check no existence of pressure hydraulic command in the relay ( -m). . check for sufficient inlet pressure. . create demand/flow, confirm pilot setting. . check that the...
https://www.bermad.com/wp-content/uploads/2016/05/IR-920-M0-50-R.pdf
pressure is stabilized lock the pilot nut. . open fully the downstream isolating valve. . connect the remote control to the opening port in the shuttle valve ( -x-m). iom ir- -m - -rbz trouble-shooting: symptoms cause remedy valve fails to open . cock valve position ( ). . hydraulic control command. . not
sufficient inlet pressure. . not sufficient flow. . adjusting screws. . check cock valve ( ) positioning on auto. . check no existence hydraulic command in the shuttle valve . . check for sufficient inlet pressure. . create demand/flow, confirm pilot setting. . check that the pilot adjusting screw is...
https://www.bermad.com/wp-content/uploads/2016/05/IR-920-M0-50-bRZ.pdf